PUMP HOT ALARM/INDICATOR DOES NOT OPERATE WHEN TESTED OR PUMP OVERHEAT CONDITION (PUMP OPERATOR'S PANEL) - Continued
PUMP HOT ALARM/INDICATOR DOES NOT OPERATE WHEN TESTED OR PUMP OVERHEAT CONDITION (PUMP OPERATOR'S PANEL) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 2 Page Navigation
  179    180    181    182    183  184  185    186    187    188    189  
img
DRAFT
TM 5-4210-249-13&P-2
0138
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03695
Step 13.
Turn battery disconnect switch to OFF position (WP 0007). Open pump operator's
panel housing (WP 0325). Remove primer pump inline fuse (WP 0394). Check for
continuity across fuse.
If there is no continuity, replace fuse (WP 0394).
0138-9