DRAFT
TM 5-4210-249-13&P-1
FIELD LEVEL MAINTENANCE
FOAM A TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY
INITIAL SETUP:
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Tools and Special Tools
References (continued)
Lead Set, Test (WP 0622, Item 21)
WP 0322
Tool Kit, General Mechanic's: Automotive
WP 0325
(WP 0622, Item 27)
WP 0401
WP 0439
Personnel Required
WP 0441
MOS 63B Wheeled vehicle mechanic (2)
WP 0443
WP 0455
References
WP 0459
TM 9-2320-325-14&P
WP 0499
WP 0540
WP 0550
Equipment Conditions
WP 0191
Engine OFF (TM 9-2320-347-10)
WP 0281
Parking brake applied (TM 9-2320-347-10)
WP 0311
Wheels chocked (TM 9-2320-347-10)
WP 0316
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
FOAM A TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY
NOTE
FOAM LEVEL indicators operate as follows: "E" indicator will flash when the foam level in
tank is below 1/4 full. Indicators "E" and "1/4" will illuminate when foam tank is 1/4 full.
Indicators "E", "1/4", and "1/2" will illuminate when foam tank is 1/2 full. Indicators "E",
"1/4", "1/2", and "3/4" will illuminate when foam tank is 3/4 full. And indicators "E", "1/4",
"1/2", "3/4", and "FULL" will illuminate when foam tank is full.
FOAM LEVEL gauge "E" indicator will illuminate or flash whenever power is applied to
gauge.
Foam level probe is designed and calibrated to detect class A foam. Substituting class A
foam with other liquids will send a false signal to FOAM LEVEL gauge. If it is suspected
that foam system has been contaminated or compromised with different brands and/or
types of foam, drain foam tank (WP 0031) and fill with class A foam.
0102-1