PUMP AND PLUMBING BLOW-OUT PROCEDURES
PUMP AND PLUMBING BLOW-OUT PROCEDURES - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  185    186    187    188    189  190  191    192    193    194    195  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0044
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
TFFT01230P
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
WARNING
ICON 66
Driver side pre-connect A and B hoses must be disconnected prior to performing
blow-out procedure. Hoses may become pressurized, causing injury to personnel
and/or damage to equipment.
4.
Disconnect driver side pre-connect A hose (1) and driver side pre-connect B hose (2) from two
pre-connects (3).
5.
Drain water tank (WP 0029).
6.
Open MASTER DRAIN valve (4).
NOTE
Perform Step (7) only if foam system and foam agent tanks are going to be left in a "dry
condition".
7.
Drain and flush foam agent from foam tank (WP 0032).
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
TFFT00996P
8.
Remove cap (5) from PASSENGER SIDE AUXILIARY INLET (6).
9.
Remove blow-out adapter (7) from stowage and install on PASSENGER SIDE AUXILIARY INLET (6).
0044-2