WINDSHIELD DELUGE SYSTEM DOES NOT OPERATE PROPERLY - Continued
WINDSHIELD DELUGE SYSTEM DOES NOT OPERATE PROPERLY - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  1028    1029    1030    1031    1032  1033  1034    1035    1036    1037    1038  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0125
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT02771
Step 13.
Remove relay P6 from pump house power distribution block (WP 0413). Turn battery
disconnect switch to ON position (WP 0007). Put WINDSHIELD DELUGE switch to on
position (WP 0004). Check for 22 to 28 VDC between wire 2769 (red) at pump house
power distribution block relay P6, terminal 1 and a known good ground.
If 22 to 28 VDC are not present, go to Step 21.
0125-12