DIRECT TANK FILL VALVE DOES NOT OPERATE PROPERLY (AUTO OR MANUAL MODE) - Continued
DIRECT TANK FILL VALVE DOES NOT OPERATE PROPERLY (AUTO OR MANUAL MODE) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  669    670    671    672    673  674  675    676    677    678    679  
img
DRAFT
TM 5-4210-249-13&P-1
0105
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT02780
Step 6.
Remove relay P1 (WP 0413). Disconnect valve control wire harness auto tank fill
connector. With a test lead set, check for continuity across wire 2315 (yellow) from
pump house power distribution wire harness relay P1 connector, terminal 5, to valve
control wire harness auto tank fill connector, terminal A.
If there is no continuity, go to Step 21.
0105-5