DRAFT
TM 5-4210-249-13&P-1
0060
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT02765
WARNING
ICON 72
Before operating foam system, personnel must familiarize themselves with all
procedures and instructions regarding water pump, discharge devices, and foam
making devices. Failure to comply may result in injury to personnel and/or damage
to equipment.
CAUTION
Do not mix different types or brands of foam agent in foam cell or piping. Mixing of
different foam agents (either type or manufacturer) may cause deterioration of foam
agent, improper proportioning, and poor performance in a fire situation. Mixing of
Class A and/or Class B and different types of foam agents may result in a chemical
reaction which can create globules, which can clog orifices and cause system
failure.
NOTE
Test should be done using both Foam A and Foam B separately from pump operator's
panel.
Step 1.
Open pump operator's panel (WP 0019). Check pump operator's panel FOAM LEVEL
If foam level gauge indicates E (empty) (WP 0004), fill foam
0060-2