PUMP PRIMING SYSTEM DOES NOT OPERATE PROPERLY - Continued
PUMP PRIMING SYSTEM DOES NOT OPERATE PROPERLY - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  867    868    869    870    871  872  873    874    875    876    877  
img
. . .
DRAFT
TM 5-4210-249-13&P-1
0115
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04145
Step 35.
Turn battery disconnect switch to OFF position (WP 0007). Remove pump prime primer
valve inline fuse (WP 0261). Turn battery disconnect switch to ON position (WP 0007).
While an assistant pushes pump operator's panel PUMP PRIMER switch (WP 0004),
check for 22 to 28 VDC between pump house wire harness pump prime primer valve
inline fuse holder, terminal wire 4064 (red) and a known good ground.
If 22 to 28 VDC are not present, replace pump primer valve control solenoid
(WP 0266).
Step 36.
Check for continuity across pump prime primer valve inline fuse from terminal to
terminal.
a.
If continuity is present, repair wire 4065 in pump house wire harness if
repairable (TM 9-2320-325-14&P), or replace pump house wire
harness (WP 0458).
b.
If continuity is not present, replace pump prime primer valve inline fuse
(WP 0261).
0115-21