FOAM B TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY - Continued
FOAM B TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  603    604    605    606    607  608  609    610    611    612    613  
img
. . .
DRAFT
TM 5-4210-249-13&P-1
0103
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT02573A
Step 4.
Open hose bed covers (WP 0015). Turn battery disconnect switch to OFF
position (WP 0007). Remove foam tank level probe cover (WP 0281). Check foam
level probe vent tube for kinks, blockage, and damage.
If foam level probe vent tube is kinked, blocked, or damaged, remove
blockage or replace foam level probe (WP 0281).
WARNING
ICON 3
Remove rings, wristwatches, neck chains, and any other jewelry before working
around vehicle. Jewelry can catch on equipment and cause serious injury. Jewelry
and tools may short across electrical circuits and cause damage to equipment, or
severe burns or electrical shock to personnel.
Step 5.
Calibrate pump operator's panel foam level gauge (WP 0191). Turn battery disconnect
switch to ON position (WP 0007). Check if pump operator's panel FOAM B LEVEL
gauge indicates correct foam level in tank after calibration of pump operator's panel
foam level gauge has been performed.
a.
If pump operator's panel FOAM B LEVEL gauge indicates correct foam
level in tank, fault corrected.
b.
If pump operator's panel FOAM B LEVEL gauge does not indicate
correct foam level in tank, replace foam level probe (WP 0281).
0103-3