FOAM B TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY - Continued
FOAM B TANK LEVEL INDICATOR GAUGE DOES NOT OPERATE PROPERLY - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  606    607    608    609    610  611  612    613    614    615    616  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0103
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT02603
Step 8.
Turn battery disconnect switch to OFF position (WP 0007). Open pump operator's
panel housing (WP 0325). Disconnect cab foam level gauge wire harness connector
from pump operator's panel FOAM B LEVEL gauge. Remove cab instrument panel A
(WP 0311). Disconnect cab foam level gauge wire harness connector from cab FOAM
B LEVEL gauge. With a test lead set, check for continuity across cab foam level gauge
wire harness from pump operator's panel FOAM B LEVEL gauge connector, terminal 1
to cab FOAM B LEVEL gauge connector, terminal 1. Note reading. Repeat continuity
checks for terminals 2 to 2, 3 to 3, 4 to 4, 5 to 5, 6 to 6, and 7 to 7.
a.
If there is continuity across all terminals of cab foam level gauge wire
harness, replace pump operator's panel FOAM B LEVEL
gauge (WP 0322).
b.
If there is no continuity for any pair of terminals, replace cab foam level
gauge wire harness (WP 0439).
Step 9.
Check if pump operator's panel WATER LEVEL gauge indicators illuminate or
flash (WP 0004).
If pump operator's panel WATER LEVEL gauge indicators do not illuminate
or flash, go to Step 12.