FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued
FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  515    516    517    518    519  520  521    522    523    524    525  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0096
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04042
Step 15.
Open pump house panel A (WP 0539). Check if eductor valve is in open position.
If eductor valve is not in open position, troubleshoot Foam Not Delivered
From All Systems (Bumper Turret, Ground Sweeps, and Manual Metering
Controls) or System Does Not Shut Off (WP 0094).
TFFT04416
Step 16.
While an assistant puts pump operator's panel FOAM TANK switch to "A" position and
back to "B" position (WP 0004), check if foam B shutoff valve operates to closed and
open position.
If foam B shutoff valve does not operate to closed and open positions, go
to Step 18.