TM 5-4210-249-13&P-1
0096
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04042
Step 15.
Open pump house panel A (WP 0539). Check if eductor valve is in open position.
If eductor valve is not in open position, troubleshoot Foam Not Delivered
From All Systems (Bumper Turret, Ground Sweeps, and Manual Metering
TFFT04416
Step 16.
While an assistant puts pump operator's panel FOAM TANK switch to "A" position and
back to "B" position (WP 0004), check if foam B shutoff valve operates to closed and
open position.
If foam B shutoff valve does not operate to closed and open positions, go
to Step 18.
0096-10