FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued
FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  514    515    516    517    518  519  520    521    522    523    524  
img
. . .
DRAFT
TM 5-4210-249-13&P-1
0096
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04527
Step 13.
Put personnel cab FOAM SELECT switch to A position and back to B
position (WP 0004). Check if personnel cab foam B indicator illuminates.
If personnel cab foam B indicator illuminates, go to Step 15.
TFFT04419
Step 14.
Turn battery disconnect switch to OFF position (WP 0007). Remove personnel cab
instrument panel B (WP 0311). While an assistant holds personnel cab FOAM SELECT
switch in B position (WP 0004), check for continuity across switch from terminal wire
2830 (red) to terminal wire 2843 (red).
a.
If there is continuity, repair wire 2830 in cab pump control wire harness
if repairable (TM 9-2320-325-14&P), or replace cab pump control wire
harness (WP 0443).
b.
If there is no continuity, replace personnel cab FOAM SELECT
switch (WP 0308).
0096-9