DRAFT
TM 5-4210-249-13&P-1
0073
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 15.
Swap relays P7 and P8 (WP 0413). Start water pump engine (WP 0022). Check if
water pump engine starts.
a.
If water pump engine starts and stays running, replace relay P8
(WP 0413).
b.
If water pump engine starts and stops, replace pump house power
distribution wire harness and block (WP 0457).
c.
If water pump engine does not start, notify Supervisor.
END OF TASK
FOLLOW-ON MAINTENANCE
Remove wheel chocks (TM 9-2320-347-10)
END OF TASK
END OF WORK PACKAGE
0073-11/(12 blank)