TM 55-1925-292-14&P
DIRECT SUPPORT MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
FIREFIGHTING SYSTEM, REPAIR
INITIAL SETUP:
Tools and Special Tools:
References (continued):
Tool Kit, General Mechanic's (Item 1, Table 2,
Materials/Parts:
Equipment Conditions:
Tag, Danger (Item 8, Table 1, WP 0050 00)
CLOSE valve CA-6, STG AIR TO PMP DR ENG.
Monitor, Fire, Manual (Item 32, Figure 1,
Lock out and tag out (FM 55-502).
Set to OFF the AFFF PUMP circuit breaker on
the main switchboard. Lock out and tag out
(FM 55-502).
Personnel Required:
CLOSE valves FM-13, F.F. TO F.M. CRSVR and
Two Watercraft Engineers, 88L
FM-84, AFFF TK SUCT. Lock out and tag out
(FM 55-502).
References:
FM 55-502
FIRE MONITOR REPLACEMENT
REMOVAL
1. Remove the four bolts (figure 1, item 1) and four nuts (figure 1, item 2) from the fire monitor flange (figure 1,
item 3).
4
3
1
2
5
6
Figure 1. Fire Monitor
0024 00-1
|