TM 55-1925-292-14&P
DIRECT SUPPORT MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
FIREFIGHTING SYSTEM, TEST
INITIAL SETUP:
Equipment Conditions:
Personnel Required:
Diesel engine-driven firefighting pump operating
One Watercraft Engineer, 88L
normally (WP 0005 00).
One Watercraft Operator, 88K
Fire monitors pressurized (WP 0005 00).
References:
FM 55-502
FIRE HOSE TEST
Testing of the fire hoses is required annually. Refer to FM 55-502 for testing requirements and procedures.
FIRE MONITORS-FUNCTIONAL TEST
1. At each fire monitor (figure 1, item 1), direct the fire monitor to place water away from the vessel using the
directional control handle (figure 1, item 2).
2. OPEN the cutoff valve (figure 1, item 3).
3. Verify that the fire monitor (figure 1, item 1) operates without leaks.
4. CLOSE the cutoff valve (figure 1, item 3) and repeat steps 1-4 for the remaining fire monitors (figure 1, item 1).
5. When all monitors have been tested, return the equipment to the desired readiness condition.
2
1
3
Figure 1. Fire Monitor Testing
END OF WORK PACKAGE