NOTE
Recovery/recycling station will also recover refrigerant oil from air conditioner system.
Refrigerant oil will be separated from refrigerant in a container. Amount of refrigerant oil
recovered must be noted. Not all refrigerant oil will be recovered, some refrigerant oil will
stay in air conditioner system.
12. Recover all refrigerant from system to 10 to15 in. Hg vacuum on low-side gauge of recovery/recycling station.
CAUTION
Always comply with all local regulations regarding refrigerant disposal. Failure to
comply may result in penalties for improper disposal.
Air conditioner dryer must be replaced each time air conditioning system
refrigerant is evacuated or damage to system may result.
END OF TASK
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -