120-VOLT CORD REEL RECEPTACLES DO NOT OPERATE - Continued
120-VOLT CORD REEL RECEPTACLES DO NOT OPERATE - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 2 Page Navigation
  482    483    484    485    486  487  488    489    490    491    492  
img
DRAFT
TM 5-4210-249-13&P-2
0165
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03915
Step 4.
Install jumperwire between red wire at circuit breaker 4 and a known good ground.
Then check for continuity across red wire from cord reel receptacle box, red wire
connection, to a known good ground.
If there is no continuity, go to Step 16.
Step 5.
Remove jumperwire and check for continuity across red wire from cord reel receptacle
box, red wire connection, to a known good ground.
If there is continuity, go to Step 18.
0165-4