120-VOLT RECEPTACLES DO NOT OPERATE - Continued
120-VOLT RECEPTACLES DO NOT OPERATE - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 2 Page Navigation
  477    478    479    480    481  482  483    484    485    486    487  
img
DRAFT
TM 5-4210-249-13&P-2
0164
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03845
NOTE
Circuit breaker may be in ON position when tripped. To make sure circuit breaker is not
tripped, reset circuit breaker by switching it to OFF position, then back to the ON position.
Step 6.
Reset circuit breaker (WP 0021). Check for continuity across circuit breaker.
If there is no continuity, replace circuit breaker (WP 0362).
0164-5