WATER PUMP OUTPUT PRESSURE IS LOW
WINDSHIELD DELUGE SYSTEM DOES NOT OPERATE PROPERLY

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  1016    1017    1018    1019    1020  1021  1022    1023    1024    1025    1026  
img
. . . . . . .
DRAFT
TM 5-4210-249-13&P-1
0124
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03975
Step 3.
Stop water pump engine (WP 0022). Install discharge and intake caps on
vehicle (WP 0004). Install blow-out adapter on PASSENGER SIDE AUX.
INLET (WP 0044). Apply 50 psi (345 kPa) shop air to PASSENGER SIDE AUX. INLET.
Push PASSENGER SIDE AUX. INLET button to OPEN position (WP 0004). Push NO.
1 DRIVER SIDE DISCHARGE PRESSURE button (WP 0004). Check if pressure
indicated at NO. 1 DRIVER SIDE DISCHARGE is equal to value indicated at pump
operator's panel PUMP DISCHARGE gauge.
a.
If NO. 1 DRIVER SIDE DISCHARGE value is equal to PUMP
DISCHARGE gauge, replace water pump (WP 0255).
b.
If NO. 1 DRIVER SIDE DISCHARGE value is not equal to PUMP
DISCHARGE gauge, troubleshoot Digital Pressure Gauge(s) Does Not
Operate (WP 0127).
END OF TASK
FOLLOW-ON MAINTENANCE
1.
Perform post operations procedures (WP 0041)
2.
Remove Blow-out Adapter (if installed) (WP 0044)
3.
Remove wheel chocks (TM 9-2320-347-10)
END OF TASK
END OF WORK PACKAGE