FOAM NOT DELIVERED FROM ROOF TURRET - Continued
FOAM NOT DELIVERED FROM GROUND SWEEPS

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  552    553    554    555    556  557  558    559    560    561    562  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0098
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03498
Step 17.
Put ROOF TURRET switch to off position (WP 0004). Turn battery disconnect switch to
OFF position (WP 0004). With a test lead set, check for continuity across wire 2200
(black) from valve control wire harness ROOF TURRET FOAM A foam system flow
control manifold connector, terminal 2 to a known good ground.
a.
If there is continuity, replace ROOF TURRET FOAM A metering control
valve (WP 0288).
b.
If there is no continuity, repair wire 2200 in valve control wire harness if
repairable (TM 9-2320-325-14&P), or replace valve control wire
harness (WP 0463).
END OF TASK
FOLLOW-ON MAINTENANCE
Remove wheel chocks (TM 9-2320-347-10)
END OF TASK
END OF WORK PACKAGE
0098-15/(16 blank)