FOAM NOT DELIVERED WHEN TANK A IS SELECTED (BUMPER TURRET, GROUND SWEEPS, AND MANUAL METERING CONTROLS) - Continued
FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS)

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  505    506    507    508    509  510  511    512    513    514    515  
img
. . .
DRAFT
TM 5-4210-249-13&P-1
0095
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04050
Step 26.
Turn battery disconnect switch to OFF position (WP 0007). Remove personnel cab
instrument panel B (WP 0311). Turn battery disconnect switch to ON
position (WP 0007). Put personnel cab FOAM SYSTEM switch to on
position (WP 0004). Check for 22 to 28 VDC between wire 2830 (red) from personnel
cab FOAM SELECT switch, terminal to a known good ground.
a.
If 22 to 28 VDC are present, replace personnel cab FOAM SYSTEM
switch (WP 0315).
b.
If 22 to 28 VDC are not present, repair wire 2830 in cab pump control
wire harness if repairable (TM 9-2320-325-14&P), or replace cab pump
control wire harness (WP 0443).
END OF TASK
FOLLOW-ON MAINTENANCE
1.
Install skid plate grille if removed (WP 0550)
2.
Remove wheel chocks (TM 9-2320-347-10)
END OF TASK
END OF WORK PACKAGE
0095-17/(18 blank)