FOAM NOT DELIVERED WHEN TANK A IS SELECTED (BUMPER TURRET, GROUND SWEEPS, AND MANUAL METERING CONTROLS) - Continued
FOAM NOT DELIVERED WHEN TANK A IS SELECTED (BUMPER TURRET, GROUND SWEEPS, AND MANUAL METERING CONTROLS) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  491    492    493    494    495  496  497    498    499    500    501  
img
. . . .
DRAFT
TM 5-4210-249-13&P-1
0095
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04034
WARNING
ICON 3
Remove rings, wristwatches, neck chains, and any other jewelry before working
around vehicle. Jewelry can catch on equipment and cause serious injury. Jewelry
and tools may short across electrical circuits and cause damage to equipment, or
severe burns or electrical shock to personnel.
Step 5.
Turn battery disconnect switch to OFF position (WP 0007). Remove personnel cab
instrument panel A (WP 0311). Remove relay 5 from cab power distribution
block (WP 0402). Turn battery disconnect switch to ON position (WP 0007). Put
personnel cab FOAM SYSTEM switch to on position (WP 0004). Check for 22 to 28
VDC between wire 2846 (white) from cab power distribution block relay 5, terminal 3 to
a known good ground.
If 22 to 28 VDC are not present, go to Step 12.
Step 6.
Turn battery disconnect switch to OFF position (WP 0007). Check for continuity across
wire 1640 (black) from cab power distribution block relay 5, terminal 2 to a known good
ground.
If there is no continuity, replace cab power distribution wire harness and
block (WP 0441).
0095-3