TM 5-4210-249-13&P-1
OPERATOR LEVEL MAINTENANCE
120 VAC OUTLET(S) DOES NOT OPERATE
INITIAL SETUP:
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
References
Equipment Conditions
Engine OFF (TM 9-2320-347-10)
Wheels chocked (TM 9-2320-347-10)
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
120 VAC OUTLET(S) DOES NOT OPERATE
TFFT04080
Step 1.
Turn battery disconnect switch to ON position (WP 0007). Start
engine (TM 9-2320-347-10). Start hydraulic generator (WP 0021). Check if any other
120 VAC outlets do not operate.
If all 120 VAC outlets do not operate, notify Supervisor.
NOTE
Circuit breaker may be in ON position when tripped. To make sure circuit breaker is not
tripped, reset circuit breaker by switching it to OFF position and then back to ON position.
Step 2.
If cord reel outlets do not operate, check if circuit breaker 2 or 4 is tripped.
If circuit breaker 2 or 4 is tripped, reset tripped circuit breaker. If circuit
breaker trips again, notify Supervisor.
Step 3.
If driver side pump house outlets do not operate, check if circuit breaker 7 is tripped.
If circuit breaker 7 is tripped, reset tripped circuit breaker. If circuit breaker
trips again, notify Supervisor.
0051-1