TM 55-1925-292-14&P
0009 00
Auxiliary Diesel Engines, Ventilation Fans,
and/or Fuel Oil Transfer Pumps Do Not
Shut Down When the FM-200 System
is Actuated
WARNING
Does
Take great care when working
any equipment
No
around energized electrical
shut down when the
equipment. Contact between
FM-200 system is
unprotected body parts and
actuated?
electrical conductors can cause
serious injury or death.
Yes
Verify that the plunger
for PS-1 is in the DOWN
position. Measure for 24 Vdc
A
across terminals 2 and 3 inside
of pressure switch PS-1.
To Sheet 2
WARNING
Is
Take great care when working
24 Vdc
Yes
around energized electrical
present at
equipment. Contact between
pressure
unprotected body parts and
switch
electrical conductors can cause
PS-1?
serious injury or death.
No
Set the FM-200 SYSTEM
circuit breaker in the 01 and 02
emergency lighting panel 1 to
OFF and place PS-1 UP in
the OPERATE position. Measure
for continuity across pins 2 and 3
in pressure switch PS-1.
Does
Locate and repair
pressure
the faulty wiring in the
Yes
switch PS-1
engine room FM-200 relay
check
panel box.
good?
No
Pressure switch PS-1 is
faulty. Notify the
maintenance supervisor
of the defect.
Exit
Procedure 5. Auxiliary Diesel Engines, Ventilation Fans, And/Or Fuel Oil Transfer Pumps Do Not Shut
Down When The FM-200 System Is Actuated (Sheet 1 of 2)
0009 00-8