From Sheet 1
A
WARNING
Take great care when working
around energized electrical
equipment. Contact between
unprotected body parts and
electrical conductors can cause
serious injury or death.
Place pressure switch PS-1
UP in the OPERATE position
and measure for 120 Vac across
terminals 8 and 5 in pressure
switch PS-1.
Is
Locate and repair the faulty wiring
No
120 Vac
in the FM-200 system between the
present?
circuit breaker and pressure switch
PS-1.
Yes
WARNING
Take great care when working
around energized electrical
equipment. Contact between
unprotected body parts and
electrical conductors can cause
serious injury or death.
Set the FM-200 SYSTEM
circuit breaker in the 01 and 02
emergency lighting panel 1 to
Pressure switch PS-1 is
Does
OFF and place pressure switch
pressure switch No
faulty. Notify the
PS-1 UP in the OPERATE
maintenance supervisor
PS-1 check
position. Measure for
of the defect.
good?
continuity across pins
8 and 9 and pins 5 and 6
in pressure switch PS-1.
Yes
Locate and repair the
faulty wiring in the FM-200
system electrical wiring
between PS-1 and the
inoperative amber strobe
light.
Exit
Procedure 4. Amber Strobe Light Does Not Flash When The FM-200 System Is Actuated (Sheet 2 of 2)