TM 55-1925-292-14&P
0009 00
To Sheet 2
A
Do
SSDG-1, SSDG-2,
Relay R1 in the engine room
No
and the bow thruster engine
FM-200 relay panel box is
shut down when PS-1
faulty. Notify the maintenance
is placed UP in the
supervisor of the defect.
OPERATE
position?
Yes
Do the
pump drive engine,
Relay R2 in the engine room
AMS-1 supply fan, and
No
FM-200 relay panel box is
fuel oil transfer pump 2
faulty. Notify the maintenance
shut down when PS-1
supervisor of the defect.
is placed UP in the
OPERATE
position?
Yes
Do
fuel oil transfer
pump 1, engine room
Relay R3 in the engine room
supply fan 1, and engine
No
FM-200 relay panel box is
room supply fan 2 shut down
faulty. Notify the maintenance
when PS-1 is placed UP
supervisor of the defect.
in the OPERATE
position?
Yes
Exit
Procedure 5. Auxiliary Diesel Engines, Ventilation Fans, And/Or Fuel Oil Transfer Pumps Do Not Shut