TM 55-1925-292-14&P
0009 00
Amber Strobe Light Does Not Flash
WARNING
When the FM-200 System is Actuated
Take great care when working
around energized electrical
equipment. Contact between
unprotected body parts and
electrical conductors can cause
serious injury or death.
Does
any amber
Yes
strobe light flash
when the FM-200
Place pressure switch PS-1 UP in
system is
the OPERATE position, and
actuated?
measure for 120 Vac between the
black and white wires on the
inoperative amber strobe light.
No
Is
Amber strobe light
Yes
120 Vac
is faulty. Notify the
Check the condition of the FM-200
present?
maintenance supervisor
SYSTEM circuit breaker in the
of the defect.
01 & 02 emergency lighting panel 1.
No
Locate and repair the faulty circuit
in the FM-200 system electrical
wiring between PS-1 and the
inoperative amber strobe light.
Is the
circuit breaker
Reset the circuit breaker by
tripped as indicated
Yes
setting it to OFF and then setting
by the breaker being
it to the ON position.
between the ON and
OFF positions?
Exit
No
Is
the circuit
No
Set the circuit breaker
breaker in the
to the ON position.
ON position?
Yes
A
To Sheet 2
Procedure 4. Amber Strobe Light Does Not Flash When The FM-200 System Is Actuated (Sheet 1 of 2)
0009 00-6
|