CREW CAB AIR CONDITIONER SERVICE/RECHARGE - Continued
CREW CAB AIR CONDITIONER SERVICE/RECHARGE - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 2 Page Navigation
  946    947    948    949    950  951  952    953    954    955    956  
img
DRAFT
TM 5-4210-249-13&P-2
0217
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
TFFT00352A
NOTE
If system is extremely contaminated, install a receiver/dryer in-line as a prefilter for
recover/recycling station.
6.
Connect recovery/recycling station flushing drain line (4) from inlet valve side of system to receiving
container (5).
7.
Turn on recover/recycling station (6) and open inlet valve (7). Allow about 2 lb. (1 kg) of R-134a to flow
through system.
8.
Close supply line valve (8) and wait for recover/recycling station (6) to shut off.
9.
Disconnect recovery/recycling station flushing supply line (2) from outlet hose (3).
10. Disconnect recovery/recycling station flushing drain line (4) from inlet valve (7).
11. Purge system and check collection bottle for contaminants.
END OF TASK
0217-10