DIRECT TANK FILL VALVE DOES NOT OPERATE PROPERLY (AUTO OR MANUAL MODE) - Continued
DIRECT TANK FILL VALVE DOES NOT OPERATE PROPERLY (AUTO OR MANUAL MODE) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  692    693    694    695    696  697  698    699    700    701    702  
img
. .
DRAFT
TM 5-4210-249-13&P-1
0105
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT03974
Step 34.
Turn battery disconnect switch to OFF position (WP 0007). Disconnect main wire
harness valve control wire harness connector DV1. Turn battery disconnect switch to
ON position (WP 0007). With a test lead set, check for continuity across main wire
harness wire 2315 (yellow) from main wire harness valve control wire harness
connector DV1, terminal 7 to main wire harness pump operator's panel wire harness
connector DO1, terminal M.
a.
If there is continuity, repair wire 2315 in pump operator's panel wire
harness if repairable (TM 9-2320-325-14&P), or replace pump
operator's panel wire harness (WP 0459).
b.
If there is no continuity at either terminal, repair wire 2315 in main wire
harness if repairable (TM 9-2320-325-14&P), or replace main wire
harness (WP 0455).
0105-28