FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued
FOAM NOT DELIVERED WHEN TANK B IS SELECTED (BUMPER TURRET, UNDER TRUCK NOZZLES, AND MANUAL METERING CONTROLS) - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  521    522    523    524    525  526  527    528    529    530    531  
img
. . . . .
DRAFT
TM 5-4210-249-13&P-1
0096
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04425
Step 24.
Put pump operator's panel FOAM TANK switch to "A" position (WP 0004). Check if
foam A indicator illuminates (WP 0004).
If foam A indicator illuminates, go to Step 26.
TFFT04528
Step 25.
Turn battery disconnect switch to OFF position (WP 0007). Open pump operator's
panel housing (WP 0325). Turn battery disconnect switch to ON position (WP 0007).
Put pump operator's panel FOAM SYSTEM to ON position (WP 0004). Check for 22 to
28 VDC between wire 2830 (red) at FOAM TANK switch, terminal to a known good
ground.
a.
If 22 to 28 VDC are present, replace pump operator's panel FOAM
TANK switch (WP 0337).
b.
If 22 to 28 VDC are not present, repair wire 2830 in pump operator's
panel wire harness if repairable (TM 9-2320-325-14&P), or replace
pump operator's panel wire harness (WP 0459).
0096-16