|
|
TM
9-4931-363-14&P
J8-8 to energize the remaining part of the voltage divider
K3. The 28 volts is connected from contact 2 of S8-A to
network on the logic card. J8-4 provides the signal return.
K3-4, which causes K3 to latch. K3-2 and -1 apply a ground
The test signal B (test signal Pi) output at J8-7 is connected
to indicators DS14 through DS17. Refer to the logic card
through contact 3 and wiper 1 of S8-1, and through the
schematic from TM 9-1270-212-14&P. With the fail enable
previously discussed contacts of S4-1, S9, and S5-A, to the
input at J8-24 held low and the BIT initiate input at J8-9
meter input and to the phase-sensing input of the A2 card.
held high, the four indicator outputs at J8-13, -20, -14, and
-23 of the logic card are open.
(9) Refer to step 8 in figure 2-9 and in the logic card
test table. Setting S9 to position R3 connects the test signal
(3) Refer to step 2 in figure 2-9 and in the logic card
D (test signal Gk) output at J8-5 through contact 3 and
test table. When S11 is released, K3 remains latched, 28
wiper 1 of S8-J, through contact 7 and wiper 1 of S4-H,
volts dc is removed from J8-9, and the ground at J8-24 is
and through the previously discussed contacts of S9 and
removed. The TR3 comparator output at J8-33 is grounded
S5-A, to the meter input and to the phase-sensing input of
through contact 2 and wiper 1 of S8-B. The go-latch-not
the A2 card.
output at J8-26 is grounded through contact 2 and wiper 1
of S8-K. With the inputs to the logic card as specified, the
(10) Refer to step 9 in figure 2-9 and in the logic
go output at J8-13 and the EIA output at J8-23 are both 28
card test table. Setting S8 to position 3 maintains the same
volts, lighting DS14 and DS17 on the test set.
basic conditions described in step 1. The ground
(4) Refer to step 3 in figure 2-9 and in the logic card
connections are removed from J8-27 and -28. With S11
pressed, energized relays K3 and K8 provide grounds as
test table. The 10 volts ac, in phase, is connected to J8-11
discussed in paragraph (6).
to energize part of the voltage divider network on the logic
card. J8-4 provides a signal return. The test signal A (test
(11) Refer to step 10 in figure 2-9 and in the logic
signal Pj) output at J8-2 is connected through contact 2 and
wiper 1 of S8-1, through contact 7 and wiper 1 of S4-1,
card test table. When S11 is released, K3 again remains
latched, 28 volts dc is removed from J8-9, and the ground
through S9-2 and -3, and through contact 2 and wiper 1 of
at J8-24 is removed. The power fail input at J8-31 is
S5-A to the meter input, and through contact 8 and wiper 2
grounded through contact 4 and wiper 1 of S8-B. With
of S4-A to the phase-sensing input to the A2 card.
these inputs to the logic card, the pilot linkage output at
(5) Refer to step 4 in figure 2-9 and in the logic card
J8-20 and EIA output at J8-23 are each 28 volts, lighting
test table. Setting S9 to position R3 connects the test signal
DS16 and DS17 on the test set.
C (test signal TR) output at J8-3 through contact 2 and
wiper 1 of S8-J, through contact 7 and wiper 1 of S4-H,
NOTE
and through S9-1 and -3 to the meter and phase detector as
in (3) above.
The information in (12) and (13) below applies
to logic card A15, used in the EIA from
(6) Refer to step 5 in figure 2-9 and in the logic card
XM136, only. P1-15 and -17 of logic card A10,
test table. Setting S8 to position 2 maintains the same basic
used in the EIA from XM128, are not
connections described in step 1. The ground connections
connected.
are removed from J8-33 and -26. With S11 pressed, K8
energizes and again provides a ground at J8-24. K3 also
(12) Refer to step 11 in figure 2-9 and in the A15
energizes to provide grounds for indicators DS14 through
test table. The connections for the out-of-phase 10 volts ac
DS17.
and for the signal return are the same as in (7) above, as are
the connections for S5, A2, and DS19 and DS20. The test
(7) Refer to step 6 in figure 2-9 and in the logic card
signal Gj output from the logic card into J8-15 is connected
test table. When S11 is released, K3 remains latched, 28
to the meter through contact 4 and wiper 1 of S8-1,
volts dc is removed from J8-9, and the ground at J8-24 is
through contact 7 and wiper 1 of S4-H, and through
removed. The skip-not output at J8-27 is grounded through
contact 2 of S9 in the R2 position.
contact 3 and wiper 1 of S8-K. The relay drive 5 input at
J8-28 is grounded through contact 3 and wiper 1 of S8-B.
(13) Refer to step 12 in figure 2-9 and in the A15
With these inputs to the logic card, the go output at J8-13
test table. The connections for this step are the same as for
and gunner linkage output at J8-14 are each 28 volts, which
(12) above except that test signal Gi from logic card A15 is
lights DS14 and DS15 on the test set.
connected to the meter through J8-17, through contact 4
and wiper 1 of S8, and through contact 1 of S9 in the R3
(8) Refer to step 7 in figure 2-9 and in the logic card
position.
test table. The 10 volts ac, out of phase, is connected to
2-45
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |