|
|
TM 55-1925-292-14&P
GENERAL SUPPORT MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
FM-200 SYSTEM AND GALLEY FIRE SUPPRESSION SYSTEM, TEST
INITIAL SETUP:
Personnel Required:
Equipment Conditions:
Set to ON the FM-200 SYSTEM circuit breaker in
One Watercraft Engineer, 88L
120V main deck, 01 & 02 emergency lighting
One Manufacturer Trained Certified Technician
panel No. 1.
FM-200 system set for normal operation
References:
DA Form 4640
DA Form 4993
SSDG 1, SSDG 2, bow thruster engine, and diesel
TM 55-1925-273-10
engine firefighting pump engines operating un-
loaded (TM 55-1925-273-10).
EDG ready to accept a load, or the vessel is operat-
ing on shore power.
ANNUAL CERTIFICATION REQUIREMENTS:
A manufacturer trained and certified technician shall accomplish the following tasks:
1. Inspect all FM-200 firefighting system components, including the compressed gas cylinders, the control
heads, mechanical wiring, electrical wiring, audible alarms, visible alarms, and all local and remote control
stations.
2. After the inspection is completed, the manufacturer trained and certified technician shall recertify the FM-200
firefighting system by performing the following:
a. The technician shall complete the manufacturer required forms and once completed, post the forms
near the applicable firefighting system for inspection purposes.
NOTE
All compressed gas cylinders must have current hydrostatic test dates stamped into the
cylinder near the valve assembly.
b. Additionally, each FM-200 firefighting system component must have (near the control head or storage
cabinet) a signed and dated tag posted by the manufacturer trained and certified technician.
3. The crew shall annotate the vessel's DA Form 4640 (Harbor Boat Deck Department Log for Class A&B
Vessels) and DA Form 4993 (Harbor Boat Engine Department Log for Class A and C-1 Vessels) indicating
the results of the manufacturer trained and certified technician's annual certification.
SEMIANNUAL CERTIFICATION REQUIREMENTS:
A manufacturer trained and certified technician shall accomplish the following tasks:
1. Inspect the galley fire suppression system components, including the compressed gas cylinders, the dis-
charge nozzles, manual pull station, mechanical wiring, electrical wiring, and fusible links.
2. After the inspection is completed, the manufacturer trained and certified technician shall recertify the galley
fire suppression system by performing the following:
a. The technician shall complete the manufacturer required forms and once completed, post the forms
near the control cabinet for inspection purposes.
0041 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |