TM 55-1925-292-14&P
DIRECT SUPPORT MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
FM-200 SYSTEM, REPAIR
INITIAL SETUP:
References (continued):
Tools and Special Tools:
Tool Kit, General Mechanic's (Item 1, Table 2,
Multimeter (Item 3, Table 2, WP 0046 00)
Materials/Parts:
Equipment Conditions:
Tag, Danger (Item 8, Table 1, WP 0050 00)
Set to OFF the FM-200 SYSTEM. circuit breaker in
Tape, Antiseizing (Item 9, Table 1, WP 0050 00)
120V main deck 01 & 02 emergency lighting
panel No. 1. Lock out and tag out (FM 55-502).
Personnel Required:
Set to OFF the EMERGENCY DIESEL GENERA-
Two Watercraft Engineers, 88L
TOR SET BATTERY CHARGER. circuit breaker
in 120V emergency load center distribution panel.
References:
Lock out and tag out (FM 55-502).
FM 55-502
TB 43-0218
WARNING
Never reuse locking hardware. Reuse of locking hardware such as lockwashers,
locking nuts, cotter pins, and lock wire can result in undetected loosening of
fastening hardware causing catastrophic component failure resulting in death,
injury, or damage to equipment. In accordance with TB 43-0218, ensure that all
locking hardware is discarded upon removal and replaced with new.
DISCHARGE NOZZLE REPLACEMENT
REMOVAL
! CAUTION
Never attempt to connect union connections with only one wrench. Damage to the
vessel's piping or to the switch's piping could occur. Always use two wrenches.
1. Use a wrench to loosen the discharge nozzle (figure 1, item 1).
2. Remove the discharge nozzle (figure 1, item 1) from the pipe fitting (figure 1, item 2).
0032 00-1
|