TM 55-1925-292-14&P
OPERATOR MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION
Table 1. Operator Preventive Maintenance Checks and Services
ITEM INTERVAL
MAN-
ITEM TO BE
PROCEDURE
EQUIPMENT
NO.
HOUR
CHECKED OR
NOT READY/
SERVICED
AVAILABLE IF:
DIESEL ENGINE-
DRIVEN FIRE-
FIGHTING PUMP
1
Before
0.2
Pump
Check oil level in the sight glass.
Oil level low.
Proper oil level is in the center of the
sight glass. Remove the breather and
add oil as required. Refer to table 2
for the proper oil.
BREATHER
SIGHT GLASS
2
Before
0.2
Fire Flap Pull
Check that all fire flap pull cables are
Any fire flap is
Cables
in the SET position (T handle pushed
deployed.
all the way IN).
Check all T handles, cable ends, and
Any T handle
attaching hardware (cotter pins, clevis
or hardware is
pins, etc.) are installed and
damaged or
undamaged.
missing.
0012 00-1
|