TM 55-1925-292-14&P
0008 00
FM-200 System Does Not
Discharge When Actuated
Locally
NOTE
To be performed by
certified technician.
Does the
release lever on
No
the local control
valve operate
freely?
Yes
Are the
hoses intact
Yes
between the CO2
cylinder and
the FM-200
cylinder?
Local control valve
No
requires repair. Notify
the maintenance
supervisor of the
defect.
Hoses are damaged.
Notify the maintenance
supervisor of the defect.
Exit
Procedure 5. FM-200 System Does Not Discharge When Actuated Locally
0008 00-6
|