TM 55-1925-292-14&P
0008 00
FM-200 System Does
Not Discharge When
Actuated Remotely
NOTE
To be performed by
certified technician.
Does the
No
T handle pull
out from the
box?
Yes
Does the
T handle pull
Yes
out more than
14" from the
box?
No
Is the
discharge head
No
mounted on the
CO2
cylinder?
Yes
Are the
hoses intact
No
between the CO2
cylinder and FM-200
cylinder?
FM-200 system requires
repair. Notify the maintenance
Yes
supervisor of the defect.
Notify the maintenance
supervisor of the need to
recharge and retest the
FM-200 system.
Exit
Procedure 4. FM-200 System Does Not Discharge When Actuated Remotely
0008 00-5
|