TM 55-1925-292-14&P
OPERATOR, UNIT, DIRECT SUPPORT, AND GENERAL SUPPORT MAINTENANCE
FIREFIGHTING, FIRE ALARM, AND FIRE SUPPRESSION SYSTEMS FOR
INLAND AND COASTAL LARGE TUG (LT)
OPERATION UNDER UNUSUAL CONDITIONS
INITIAL SETUP:
Personnel Required:
References:
One Watercraft Engineer, 88L
S6226-NM-MMC-010/15852 REV B
Two Crewmembers, Any MOS
TM 55-1925-273-10
SECURITY MEASURES FOR ELECTRONIC DATA
No electronic data is used or stored in the firefighting, fire alarm, and fire suppression systems aboard the LT.
UNUSUAL ENVIRONMENT/WEATHER
There are no environmental or weather conditions that will prevent the firefighting systems from operating.
PRESSURIZE THE FIRE MAIN WITH THE ENGINE-DRIVEN FIREFIGHTING PUMP
NOTE
This procedure is to be accomplished only upon the loss of fire and general service
pumps 1 and 2.
1. In AMS 2, at the fire and general service pumps, CLOSE the following valves:
a. FM-16, FIRE/G.S. NO.1 DISCH TO FM (figure 1, item 1)
b. FM-14, FIRE/G.S. NO.2 DISCH TO FM (figure 1, item 2)
2
1
Figure 1. Fire and General Service Pump Valves
0006 00-1
|