TM 55-1905-243-24&P
Item
Maintenance
No.
Interval
Item to be Inspected
Level
Procedure
7
Post system
FM-200 piping and
General Support
Test piping and distribution system per
disassembly
distribution system
testing requirements identified on
Drawing LCU-2K-5553-1.
8
Post system
Complete FM-200
General Support
Obtain services of Manufacturer's
activation
system
Certified Technical Representative to
perform System Recertification.
PREVENTATIVE MAINTENANCE CHECKS AND SERVICES (PMCS) FOR A/C AND EMERGENCY
GENERATOR ROOM FM-200 SYSTEM. The following identifies the PMCS required to maintain the A/C and
Emergency Generator Room FM-200 system in a fully operational condition:
Item
Maintenance
No.
Interval
Item to be Inspected
Level
Procedure
1
Monthly
Pressure, FM-200
Crew
Check pressure gauge for proper
cylinder
operating pressure-if pressure gauge
indicator is not in green, submit Work
Order to General Support (GS) Maint.
to have cylinder recharged.
2
Monthly
Complete FM-200
Crew
Inspect system components in
System
accordance with instructions contained
in Section II of this document. If any
component is damaged, submit Work
Order to General Support (GS) Maint.
3
Quarterly
Ventilation covers
Crew
Operate and service A/C and
Emergency Generator Room natural
intake, power supply, air conditioning
vent plenum and engine exhaust
covers.
4
Semi-Annually
FM-200 Pressure
Crew
Ensure diesel engine and powered
Switches
ventilation system shutdowns are in
operation. Manually raise plunger on
Pressure Switches. Confirm automatic
shutdown of diesel engine and
ventilation system. Confirm activation
of Warning Light, Electric Horn/Strobe,
and Warning Bell. Reset plunger on
Pressure Switches. If diesel engine or
ventilation system fail to shutdown
automatically, submit Work Order to
General Support (GS) Maintenance. If
Warning Light, Electric Horn/Strobe, or
Warning Bell fails to operate, repair
component. Refer to Appendix A,
Safety Bulletins for Warning Bell repair
procedure.
5
Annually
Complete FM-200
General Support
Obtain services of Manufacturer's
system
Certified Technical Representative and
perform Annual Recertification.
5