Click here to make tpub.com your Home Page

Page Title: PREVENTATIVE MAINTENANCE CHECKS AND SERVICES (PMCS) FOR FM-200 SYSTEM.
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 55-1905-243-24&P
PREVENTATIVE MAINTENANCE CHECKS AND SERVICES (PMCS) FOR FM-200 SYSTEM.
SYSTEM MAINTENANCE.  In order to ensure each FM-200 system operates as designed and installed,
Preventative Maintenance Checks and Services (PMCS) must be performed in accordance with the following
requirements.
PREVENTATIVE MAINTENANCE CHECKS AND SERVICES (PMCS) FOR ENGINE ROOM FM-200 SYSTEM.
The following identifies the PMCS required to maintain the Engine Room FM-200 system in a fully operational
condition:
Item
Maintenance
No.
Interval
Item to be Inspected
Level
Procedure
1
Monthly
Pressure, FM-200
Crew
Check pressure gauges for proper
cylinders
operating pressure. If pressure gauge
indicator is not in green, submit Work
Order to General Support (GS)
Maintenance to have cylinder recharged.
2
Monthly
Liquid level, FM-200
Crew
Take liquid level readings in accordance
cylinders*
with instructions contained in Section II of
this document. If liquid level is low,
submit Work Order to General Support
(GS) Maintenance to have cylinder
recharged.
3
Monthly
Complete FM-200
Crew
Inspect system components in
System
accordance with instructions contained in
Appendix C of this document. If any
component is damaged, submit Work
Order to General Support (GS)
Maintenance.
4
Quarterly
Ventilation dampers and
Crew
Operate and service Engine Room Supply
closures
Air Dampers (Port and Starboard), Engine
Room Exhaust Air Dampers (Port and
Starboard), and Tunnel watertight vent
closures.
5
Semi-Annually
FM-200 Pressure
Crew
Ensure all diesel engines and powered
Switches
ventilation systems shutdowns are in
operation. Manually raise plunger on
Pressure Switches. Confirm automatic
shutdown of operating engines and
ventilation systems. Confirm activation of
Warning Lights, Electric Horn/Strobe and
Warning Bell. Reset plunger on Pressure
Switches. If any engine or ventilation
system fails to shutdown automatically,
submit Work Order to General Support
(GS) Maintenance. If any Warning Lights,
Electric Horn/Strobe or Warning Bell fail
to operate, repair component. Refer to
Appendix A, Safety Bulletins for Warning
Bell repair procedure.
6
Annually
Complete FM-200
General Support
Obtain services of Manufacturer's
system
Certified Technical Representative and
perform Annual Re-Certification.
1