MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
If indicator is not illuminated, put TANK TO PUMP switch to OPEN position
(WP 0004) and release. If indicator does not remain illuminated when
switch is released, notify Supervisor.
Step 4.
If pumping from draft (WP 0025), check if suction hose is free from blockage.
If suction hose is blocked, removed blockage and go to Step 6.
TFFT03680
Step 5.
If pumping from draft (WP 0025), check if suction hose is placed so vertical height
between suction hose strainer and water pump is not more than 10 ft. (3 m).
If vertical height between suction hose strainer and water pump is more than
10 ft. (3 m), reposition vehicle to reduce vertical height and go to Step 6.
0065-3