|   |  | 
TRUCK SERVICE MANUAL
TM 5-4210-230-14&P-1
BODIES AND CABS
COMPONENT PROBLEM ANALYSIS
COMPRESSOR
Some possible failings of the compressor include:
1.
Leaking    Front    Seal    This    allows    refrigerant    and
lubricating   oil   to   escape   from   system   in   loss   of
cooling and damage to compressor.
2.
Bearing  Failure  Usually  the  result  of  material  wear
but  can  result  from  excessive  drive  belt  tension  or
pulley misalignment.
3.
Burned-Up Compressor Caused by lack of lubricating
oil.    This  emphasizes  the  need  for  checking  the  oil
level in the compressor at the time of system service.
In the event that compressor failure is severe enough
to form metal particles, purge compressor discharge-
to-filter-dehydrator    lines    with    4.5    kg    (1    lb.)    of
refrigerant and replace the filter-dehydrator.
For  compressor  service  procedures,  refer  to  Bodies
and  Cabs,  Section  CTS-2577  of  the  Truck  Service
Manual
MAGNETIC CLUTCH
The two most common clutch failures are:
1.
Burned-Out Facings.
2.
Broken Torque Springs.
Both   of   these   failings   are   usually   symptomatic   of
troubles    somewhere    else    in    the    system.    (Example:    A
restriction    in    the    condenser    will    cause    excessive    head
pressures,  which  in  turn  will  overwork  the  compressor  and
clutch, eventually causing failure of one or both.)
For  clutch  service  procedures,  refer  to  Bodies  and
Cabs, Section CTS-2577 of the Truck Service Manual.
THERMOSTATIC TEMPERATURE CONTROL SWITCH
The    thermostatic    temperature    control    switch    is
relatively   trouble   free;   however,   should   it   fail,   it   must   be
replaced.    If  the  clutch  remains  engaged  continually,  check
the  sensing  tube  of  the  control  switch  to  see  that  it  has  not
been  pulled  out  of  the  evaporator  core.    The  sensing  tube
should  be  located  in  the  evaporator  core  as  shown  in  Figure
59.
Also,  make  sure  air  conditioning  (A/C)  control  cable
is properly adjusted.
CONDENSER
Possible problems with the condenser include:
1.
A leak in the condenser.
2.
A  stoppage  or  restriction  of  refrigerant  flow  through
the condenser.  This could result from some foreign
material inside the core or by a sharp bend or dent in
the condenser tubing or in the hoses leading into or
out of the condenser.
(Make   a   visual   check   to   make   sure   this   has   not
occurred.)
3.
A restriction of air flow through the condenser.  This
is  the  most  common  problem  and  results  from  dirt,
leaves, etc.  collecting on the front area.
A stoppage or restriction of refrigerant flow or air flow
through  the  condenser  will  be  indicated  by  a  high
discharge pressure reading on the test gauge.
Restriction of refrigerant flow will show a lower than
normal 
suction 
pressure 
on 
the 
test 
gauge.
Restricted   air   flow   will   build   high   discharge   and
suction pressures.
In  some  instances  tubing  may  be  replaced  or  leaks
may   be   repaired   by   silver   soldering   if   the   spot   is
accessible,    however,    a    stopped-up    or    internally
restricted core must be replaced.
CAUTION
Never weld, solder, steam clean or use any excessive amount
of  heat  on  any  of  the  refrigerant  lines  or  components  of  the
refrigeration   system   while   the   system   is   charged.      Heat
applied to any part would cause-the pressure of the refrigerant
within the closed system to become excessive.
EXPANSION VALVE
Possible problems at the expansion valve include:
1.
Stoppage - Stoppage in the system tends to occur at
the valve or at the filter-dehydrator tank.
2.
Valve   Sticking   -   The   valve   tends   to   stick   closed
cutting  off  the  refrigerant  supply  to  the  evaporator
and stopping all cooling from the air conditioner.
 
 |