|   |  | 
TRUCK SERVICE MANUAL
TM 5-4210-230-14&P-1
BODIES AND CABS
4.
Remove   dipstick   and   measure   wetted   portion   to
determine oil level in compressor.  Compare oil level
reading 
with 
specified 
oil 
level 
listed 
in
SPECIFICATIONS.
If  necessary,  add  refrigeration  oil  to  obtain  specified
level.  (Refer to SPECIFICATIONS for oil type.)
If  oil  level  is  higher  than  specified,  draw  out  excess
oil to obtain correct level.
After establishing correct oil level, reinstall oil fill plug
and  gasket.    Tighten  plug  to  torque  value  listed  in
TORQUE CHART
Reinstall compressor on engine, if removed.
EVACUATING THE AIR CONDITIONING SYSTEM
Whenever the air conditioning refrigerant system has
been  opened,  it  is  necessary  that  the  system  be  completely
evacuated of air and moisture before being recharged.
Outlined  below  is  the  procedure  for  evacuating  the
system using the SE-2443 Portable Service Station.
1.
Connect SE-2443 Service Station to air conditioning
system service ports as follows:
a.
Close  all  valves  on  service  station  (turn  fully
clockwise).
b.
Connect   suction   gauge   hose   to   compressor
suction service port.
c.
Connect discharge gauge hose to compressor
discharge service port.
d.
Connect  hose  from  center  fitting  on  manifold
to   vacuum   pump   suction   fitting   on   service
station.
e.
Open  manifold  suction  and  discharge  gauge
valves (turn fully counterclockwise).
2.
Start vacuum pump and SLOWLY open pump blank
off valve.
3.
After suction gauge on manifold shows that vacuum
is   being   established   in   the   system,   open   vacuum
gauge   valve   on   service   station   and   continue   to
operate vacuum pump for ten (10) minutes.
4.
Close  pump  blank  off  valve  and  observe  electronic
vacuum gauge for one (1) minute.  The meter should
not   indicate   a   rise   of   more   than   5   millimeters   of
mercury.    If  gauge  rises  more  than  5  millimeters  of
mercury in one (1) minute, system has a leak which
must be repaired.
5.
Open  pump  blank  off  valve  and  continue  to  operate
vacuum pump for an additional twenty (20) minutes.
Then    close    pump    blank    off    valve    and    observe
electronic   vacuum   gauge.      If   meter   reading   stays
below  4  millimeters  of  mercury  for  two  (2)  minutes,
system is ready to be charged.
6.
With    vacuum    pump    still    operating,    close    both
manifold   gauge   valves,   pump   blank   off   valve   and
vacuum meter valve.  Turn off vacuum pump.
Do    not    disconnect    manifold    gauge    hoses    from
compressor    service    ports    prior    to    charging    the
system.
CHARGING    THE    AIR    CONDITIONING    SYSTEM    (FULL
CHARGE)
In    preparation    for    charging,    the    air    conditioning
system  must  be  evacuated  of  all  air  and  moisture  and  be
completely  leak  free.    (See  "Evacuating  the  Air  Conditioning
System".)
To charge the system, utilizing the SE-2443 Portable
Service    Station    and    SE-2448    Heated    Charging    Cylinder,
proceed as follows:
1.
Manifold suction and discharge gauge hoses remain
connected 
to 
compressor 
service 
ports 
from
evacuating operation.
2.
Fill  SE-2448  Charging  Cylinder  with  2.25  kg  (5  lbs.)
of   refrigerant.      (Follow   equipment   manufacturer's
instructions.)    Make    sure    all    valves    on    charging
cylinder are closed after filling.
3.
Connect  service  hose  from  center  manifold  fitting  to
bottom valve on charging cylinder.
4.
Open  bottom  valve  on  charging  cylinder  and  loosen
center  hose  connection  at  manifold  for  10  seconds,
or  until  hose  fitting  becomes  cold,  to  purge  air  from
hose; then tighten hose connection.
5.
With  the  engine  shut  off,  open  manifold  discharge
gauge valve and fill air conditioning system with 2 kg
(4.5  lbs.)  of  refrigerant.    (Follow  charging  cylinder
manufacturer's instructions.)
DO  NOT  overcharge  the  system.    Excessively  high
head   pressures   during   operation   will   result   from
overcharging.
6.
When    system    is    fully    charged,    close    manifold
discharge    valve    and    bottom    valve    on    charging
cylinder.    Slowly  loosen  hose  connection  at  bottom
valve    on    charging    cylinder    and    allow    refrigerant
pressure   to   bleed   off;   then   disconnect   hose   from
valve.
CTS-2731   Page 23
PRINTED IN UNITED STATES OF AMERICA
 
 |