TM 5-4210-218-13&P
4-18.1.2 Installation.
a.
Check new Halon cylinder adapter (3) for defects.
b.
Wrap Halon cylinder adapter with one layer of antiseize tape (item 3, Section II, Appendix F).
c.
Holding pipe tee (2) securely, screw new Halon cylinder adapter into pipe tee and tighten securely.
d.
Connect assembly to Halon hose, install on Halon cylinder valve and test for leaks using leak detector
(Appendix E).
4-18.2 Gauge Replacement.
4-18.2.1 Removal.
a.
Holding pipe tee (2) securely, unscrew gauge (4) from pipe tee and discard.
b.
Make certain pipe tee threads are cleaned of any remaining antiseize tape.
4-18.2.2 Installation.
a.
Check new gauge (4) for defects.
b.
Wrap gauge threads with one layer of antiseize tape (item 3, Section II, Appendix F).
c.
Holding pipe tee (2) securely, screw gauge (4) into pipe tee (2) and tighten securely.
d.
Install assembly and check for leaks using leak detector (Appendix E).
4-18.3 Quick Disconnect Plug Replacement.
4-18.3.1 Removal.
a.
Hold pipe nipple (5) securely, unscrew plug (6) from nipple and discard.
b.
Clean any remaining antiseize tape from nipple threads.
4-18.3.2 Installation.
a.
Check new plug (6) for defects.
b.
Wrap plug threads with one layer of antiseize tape (item 3, Section II, Appendix F).
c.
Screw plug (6) onto pipe tee (2) and tighten securely.
d.
Install adapter on Halon cylinder and test for leaks using leak detector (Appendix E).
4-18.4 Pipe Tee Replacement.
4-18.4.1 Removal.
a.
Perform step a of procedure 4-18.2.1.
b.
Perform step b of procedure 4-18.1.1.
c.
Holding nipple securely, unscrew pipe tee (2) and lay aside for disposal.
4-24
|