12
Quarterly
2.0
Pump
Service the diesel engine-driven fire-
fighting pump (WP 0015 00).
BREATHER
SIGHT GLASS
FIRE DETECTION
SYSTEM
13
Semiannual
0.2
Supervisory
Move the RESET/LAMP TEST switch
Any control
Circuits
to RESET. All visual indicators on the
panel does not
control panel should light and trouble
light, or trouble
horn should sound.
horn does not
sound.
14
Annual
4.0
Fire Hoses
Pressure test (FM 55-502).
Fire hose fails
pressure test.