TM 55-1925-292-14&P
0009 00
Fire Detection System
Fails to Activate When an
Alarm Condition is Present
Are any
Is the
indicators
TROUBLE
Notify the maintenance supervisor
illuminated on
Yes
No
LED illuminated
of the defect and perform
the fire
on the fire detection
procedure 9 in this work package.
detection panel
panel in the
in the EOS?
EOS?
No
Yes
Notify the
Is the
maintenance
POWER LED
supervisor of the
No
Yes
illuminated on the
defect, and check the
fire detection
condition of the FIRE
panel in the
DETECTION
EOS?
SYSTEM circuit
breaker in the 120 Vac
emergency distribution
panel 1.
Is the circuit
Is the
breaker tripped as
Set the circuit
No
circuit breaker
indicated by the
No
breaker to the
in the
breaker being
ON position.
ON position?
between the ON
and Off
positions?
Yes
Yes
Reset the circuit breaker by
setting it to OFF and then
setting it to the ON position.
Does the fire
detection panel
Reset the fire
return to normal
Yes
detection panel
operation with
the TROUBLE
LED not
illuminated?
No
Fire detection panel battery or battery
charging circuitry is faulty. Notify the
maintenance supervisor of the defect.
Exit
Procedure 10. Fire Detection System Fails To Activate When An Alarm Condition Is Present