0009 00
From Sheet 1
A
Does
the fire
detection panel
Yes
return to normal
operation with
the alarm
secured?
No
B
From Sheet 1
Does
1. Systematically replace each
the fire
fire pull station in the alarmed
detection panel
Yes
zone with a known good fire pull
return to normal
station (WP 0018 00).
operation with
2. Reset the fire detection panel
the alarm
secured?
No
Does
the pilothouse
The Dual zone
remote indicator
module is defective.
Yes
panel indicate that a
Notify the maintenance
zone is in an alarmed
supervisor of the
condition?
defect.
No
The multiple relay module is
defective. Notify the
maintenance supervisor
of the defect.
Exit
Procedure 8. Fire Detection Activates With No Alarm Condition Present (Sheet 2 of 2)