TM 55-1925-292-14&P
0009 00
From Sheet 1
From Sheet 1
A
B
Reset the circuit breaker by
setting it to OFF and then setting
it to the ON position.
Is
the circuit
No
Set the circuit breaker
breaker in the
to the ON position.
ON position?
Yes
Place pressure switch PS-1
UP in the OPERATE position,
and measure for 115 Vac
across terminals 8 and 5 in PS-1.
Locate and repair the
Is
faulty wiring in the FM-200
No
120 Vac
system between the
present?
circuit breaker and pressure
switch PS-1.
Yes
WARNING
Take great care when working
around energized electrical
equipment. Contact between
unprotected body parts and
electrical conductors can cause
serious injury or death.
Does
pressure
Set the FM-200 SYSTEM
Pressure switch PS-1 is
No
switch PS-1
circuit breaker in the 01 and 02
faulty. Notify the maintenance
check
emergency lighting panel 1 to
supervisor of the defect.
good?
OFF and place PS-1 up in
the OPERATE position.
Measure for continuity across
pins 8 and 9 and pins 5 and 6
Yes
in pressure switch PS-1.
Locate and repair the
faulty circuit in the FM-200
system electrical wiring
between PS-1 and junction
box FM2-JB2.
Exit
Procedure 6. Engine Room FM-200 Alarm Bell Does Not Sound When The FM-200 System is Actuated
(Sheet 2 of 2)
0009 00-11

Privacy Statement - Press Release - Copyright Information. - Contact Us