TM 55-1925-292-14&P
0006 00
8. Start the P-100 portable pump (S6226-NM-MMC-010/15852 REV B).
9. Pressurize a maximum of two fire hoses attached to the fire main.
FM-200 LOCAL ACTUATION
NOTE
Perform this procedure only in extreme emergency. If the situation is not extreme,
actuate the FM-200 fire suppression system from the main deck.
1. Perform all steps necessary for normal FM-200 fire suppression system actuation (WP 0005 00).
2. Remove the locking pin (figure 6, item 1) and OPEN the CO2 discharge valve (figure 6, item 2) by pulling the
handle (figure 6, item 3) and rotating it clockwise 180.
3. Wait 15 minutes and then begin reentry procedures (WP 0005 00).
3
1
2
2
Figure 6. CO2 Discharge Valve
BYPASS FM-200 DISCHARGE DELAY
1. Remove the locking pin (figure 7, item 1) on the discharge delay valve (figure 7, item 2).
2. OPEN the discharge delay valve (figure 7, item 2) by rotating the handle (figure 7, item 3) to the OPEN
position.
3. The FM-200 system will now discharge without the 60-second delay.
0006 00-6
|