TM 55-1925-292-14&P
0002 00
FIRE STATIONS
The fire stations are part of the raw water firefighting system. The fire stations make pressurized firefighting
water available to multiple locations on the vessel. The fire stations are capable of shooting 70 gallons (265 liters)
of water per minute (in a solid stream) approximately 75 feet (23 meters) when pressurized to 100 PSI (6.9 bar).
The technical characteristics of the fire stations are contained in table 10.
Table 10. Fire Station Technical Characteristics
Item
Data
Type ................................................................................................................... 1 inch diameter
Rated Capacity ......................................................................... 70 gallons (265 liters) per minute
Maximum Test Pressure .................................................................................. 300 PSI (20.7 bar)
Maximum Design Pressure ............................................................................. 200 PSI (13.8 bar)
Continuous Working Pressure ........................................................................... 125 PSI (8.6 bar)
Maximum Fluid Temperature .............................................................................. 125 F (51.7 C)
DIESEL ENGINE-DRIVEN FIREFIGHTING PUMP
The diesel engine-driven firefighting pump pressurizes the exterior firefighting system. It is located in AMS 1 and
draws raw water from the sea chest through a simplex strainer to prevent clogging when pressurizing the external
firefighting system. The pump is a horizontal centrifugal pump with a maximum output of 1,000 gal/min
(3,785 L/min) at 170 PSI (11.7 bar).
The technical characteristics of the diesel engine-driven firefighting pump are contained in table 11.
Table 11. Diesel Engine-Driven Firefighting Pump Technical Characteristics
Item
Data
Manufacturer ....................................................................................................................... Durco
Model ............................................................................................................................... 6 x 4/16
Type ............................................................................................................ Horizontal Centrifugal
Rated Capacity ............................................................... 1,000 gallons (3,785.4 liters) per minute
Maximum Pressure .......................................................................................... 177 PSI (12.2 bar)
Continuous Working Pressure ........................................................................... 100 PSI (6.9 bar)
Maximum Fluid Temperature .............................................................................. 125 F (51.7 C)
0002 00-26
|