DRAFT
TM 5-4210-249-13&P-1
0072
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT04770
Step 18.
Check if crew cab air conditioner condenser fans operate.
a.
If crew cab air conditioner condenser fans operate, replace crew cab
air conditioner expansion valve (WP 0213).
b.
If crew cab air conditioner condenser fans do not operate, troubleshoot
Crew Cab Air Conditioner/Heater Does Not Operate
Step 19.
Check if service/recycling station pressure gauges are above 15 PSI and 40 PSI (103-
276 kPa) low-side pressure and below 120 and 330 PSI (828-2275 kPa) high-side
pressure if air is warm.
a.
If service/recycling station pressure gauges are above 15 PSI and 40
PSI (103-276 kPa) low-side pressure and below 120 and 330 PSI (828-
2275 kPa) high-side pressure and air is warm, replace crew cab air
b.
If service/recycling station pressure gauges are not above 15 PSI and
40 PSI (103-276 kPa) low-side pressure and below 120 and 330 PSI
(828-2275 kPa) high-side pressure and air is not warm, fault corrected.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
END OF TASK
FOLLOW-ON MAINTENANCE
1.
Install crew cab bench seat if removed (WP 0501)
2.
Remove wheel chocks (TM 9-2320-347-10)
END OF TASK
END OF WORK PACKAGE
0072-13/(14 blank)