CREW CAB AIR CONDITIONER/HEATER DOES NOT OPERATE PROPERLY - Continued
CREW CAB AIR CONDITIONER/HEATER DOES NOT OPERATE PROPERLY - Continued

Maintenance Manual For Tactical Fire Fighting Truck (Tfft) Model M1142 - 1 Page Navigation
  299    300    301    302    303  304  305    306    307    308    309  
img
. . . . .
DRAFT
TM 5-4210-249-13&P-1
0070
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
TFFT 4801
Step 13.
Stop crew cab air conditioner (WP 0008). Shut vehicle engine off (TM 9-2320-347-10).
Turn battery disconnect switch to OFF position (WP 0007). Disconnect non-operating
body condenser wire harness condenser fan connector. While an assistant starts crew
cab air conditioner (WP 0008). With a test lead set, check for 22 to 28 VDC at wire
1394 from non-operating body condenser wire harness crew cab condenser fan
connector, terminal 1 to a known good ground.
If 22 to 28 VDC are not present, repair wire 1394 in body condenser wire
harness if repairable (TM 9-2320-325-14&P), or replace body condenser
wire harness (WP 0436).
Step 14.
Stop crew cab air conditioner (WP 0008). Shut vehicle engine off (TM 9-2320-347-10).
Turn battery disconnect switch to OFF position (WP 0007). With a test lead set, check
for continuity across wire 1640 from non-operating body condenser wire harness crew
cab condenser fan connector, terminal 2 to a known good ground.
a.
If continuity is present, replace non-operating air conditioner condenser
fan (WP 0199).
b.
If there is no continuity, repair wire 1640 in body condenser wire
harness if repairable (TM 9-2320-325-14&P), or replace body air
condenser wire harness (WP 0436).
0070-9